Specifiche tecniche
INPUT | |
Input Voltage: | 12 VDC |
Input Voltage range: | 11.5 ~ 16 VDC |
Electric strength max: | 18 VDC |
Fixed connect threshold: | Undervoltage: 18 VDC
Voltage drop IN/OUT: 0.6 VDC max |
Current consumption: | Rated current: 8.1 A
Max current: 9 A Current w/o Load: 100 mA Current charge: 3.5 A |
Power consumption: | Rated power: 97 W
Max power: 108 W Power charge: 42 W |
Internal input fuse: | 15 A |
Switch-on time: | 5 sec |
ENERGY STORAGE | |
Charging method: | CC / CV / CP |
Rated voltage: | 8.3 V |
End of charge voltage: | 8.3 V |
Charging current: | 16 A max |
Undervoltage protection: | 4.5 V |
Battery technology: | EDLC |
Rated capacity: | 5.73 kj (3.88 kj usefull)
1.59 Wh (1.08 Wh usefull) |
Charging time: | ~ 2 min |
Buffer time: | 30 sec |
OUTPUT | |
Output Voltage: | 12 VDC |
Output Voltage range: | (Input voltage) – 0.6 VDC |
Capacitive load: | 3000 µF (at start) |
Output current: | 8 A |
Output Power: | 96 W |
Short-circuit proof: | Yes |
No-load proof: | Yes |
Overcurrent shutdown: | 8.2 ~ 8.4 A for max 3s
8.5 ~ 10.8 A for max 100ms > 10.8A for max 5ms |
MECHANICAL & ENVIRONMENTAL CONDITIONS | |
Flammability class: | V0 |
Weight: | 0.6 kg |
UPS Connection: | Parallel: NO
Series: NO |
Degree of protection: | IP 20 |
Protection class: | III (without PE) |
Mounting type: | DIN-Rail mounting |
Housing version: | Aluminium |
Dimension: | (W)63x(H)120x(D)100 mm |
Operation Temperature: | -20 ~ +60°C |
Storage Temperature: | -30 ~ +65°C |
Max. Humidity: | ≤ 95% (at +25°C, no dew) |
Climate Class: | 3k3 (EN 60721) |
Degree of pollution: | 2 |
Overvoltage Category: | EN 61010-1: I
EN 61010-2-201: I |
CONNECTION | |
Connection INPUT/OUTPUT | Method: Screwable plug connector
Conductor cross-section: 0.129 mm² ~ 1.31 mm² Stripping length: 6 mm ~ 7 mm |
Connection RELAY | Status (configurable): Power Fail Alarm
Switching voltage: 24 VDC / 125 VAC Current Capacity: 1 A (DC) / 0.5 A (AC) State (configurable): NO / NC |
Data Interface USB | Connection Method: USB Type B (F)
Transmission physics: USB 2.0 Protocol: VCOM, HID Electrical Isolation: NO Chipset: NXP Transmission length: ≤ 3m |
Data Interface RS232 | Connection Method: DSUB 9-Pin (F) – DB9
Transmission physics: RS232 light (TX / RX) Baud Rate: 38400 Type of cable: 1:1 Electrical Isolation: NO Chipset: NXP Transmission length: ≤ 10m Voltage Level: -6 ~ +6 VDC |
INTERFERENCE IMMUNITY ACCORDING TO EN 61000 | |
Electrostatic discharge – EN 61000-4-2 | Contact discharge: 4kV
Air discharge: 8kV Comment: Criterion B |
Electromagnetic HF Field – EN 61000-4-3 | Frequency range: 80MHz ~ 1GHz
Test field strength: 10V/m Frequency range: 1.4GHz ~ 2GHz Test field strength: 3V/m Comment: Criterion A |
Fast transients (Burst) – EN 61000-4-4 | Test voltage: 2kV
Comment: Criterion A |
Surge voltage load (Surge) – EN 61000-4-5 | Test voltage L-N: ± 1kV
Test voltage L-PE, N-PE: ± 2kV Comment: Criterion A |
Power frequency magnetic field immunity – EN 61000-4-8 | Test level: 30 A/m
Comment: Criterion A |
Criterion A Normal operating behavior within the defined limits
Criterion B Temporary impairment of the operating behavior,that is corrected by the device itself
Codici di ordinazione
IPC | |||
MODEL NAME | PART NUMBER | CONFIGURATION CODE | DESCRIPTION |
UPS-96-12-S | 10005376 | B04-23C-BACH-I58365U-R08-M2D256 | IPC + 8GB RAM + M2 256GB SSD + WIFI6 |
ACCESSORIES | |||
MODEL NAME | PART NUMBER | DESCRIPTION | |
HDMI to VGA converter | 10003577 | HDMI to VGA converter |
File scaricabili
DATASHEET | ||||
NAME | VERSION | TIME | SIZE | DOWNLOAD |
UPS-96-12-S | TBD | TBD | TBD |
DRIVERS | ||||
NAME | VERSION | TIME | SIZE | DOWNLOAD |
UPS-96-12-S drivers | TBD | TBD | TBD |
MANUAL | ||||
NAME | VERSION | TIME | SIZE | DOWNLOAD |
UPS-96-12-S manual | TBD | TBD | TBD |
HARDWARE INSTALLATION GUIDE | ||||
NAME | VERSION | TIME | SIZE | DOWNLOAD |
UPS-96-12-S HIG | TBD | TBD | TBD |
Prodotti Correlati
-
UPS-96-24-S
24VDC – Industrial-grade UPS
Integrated SuperCAPS (EDLC) Battery
Up to 500 000 cycles
Capacity 5.7 kj
Corrent detection, Power Fail and Reboot function
Relay with selectable functions
Reverse polarity protection at input
Overcurrent protection & short circuit protection at output
-20 ~ +65°C
-
UPS-96-24-L
24 VDC – 96W Industrial-grade UPS
Integrated Li-Ion Battery
-
UPS-240-24-L
24 VDC @10A – 240W Industrial-grade UPS
LiFePO4 battery [64Wh] (up to 5000 cycles)